Content | Date | Cost | Contractor Rank | Address | Contractor |
---|---|---|---|---|---|
SCORE 65 Date: March 10, 2016 Contractor: Iron Horse Concrete And Construction Llc Permit type: Fire | Permit status: In for review | Permit id: Bld2016-02206 | |||||
SCORE 65 Date: September 15, 2015 Contractor: Iron Horse Concrete And Construction Llc Permit status: Inspections | Current use: Commercial | Permit id: Bld2015-07480 | |||||
SCORE 65 993 S Bending River Rd Salt Lake City Ut 84104 0000 Revised underground fire line will also require approval from public utilities. Water mains and laterals shall be provided with thrust blocks and be sized as required by national fire protection association standard 24. Water laterals that supply water based fire protection shall be ferrous pipe when it passes through a foundation wall or under footing and foundation walls in accordance with nfpa 13 & 24. Fdc shall be located on the certified address side of the structure. Fdc shall be within 1 feet of a fire hydrant. Date: March 10, 2016 Contractor: Iron Horse Concrete And Construction Llc Permit type: Fire | Permit status: Void | Current use: Commercial | Permit id: Bld2016-02206 |