Content | Date | Cost | Contractor Rank | Address | Contractor |
---|---|---|---|---|---|
SCORE 95 Electrical - a c unit must be identified with unit number. A c unit must have a means of disconnect within sight of equipment (required on roof next to unit). All wiring must be ran in approved conduit. Exposed romex shall not be used between the wall and the a c unit. Electrician needs to verify that breakers in panels are sized correctly. A service receptacle must be installed for service work. No exterior changes proposed or approved. Reference cpl2017-00944. Client: Steven Kless | Permit type: Electrical | Permit status: Cmp | Completion date: November 1, 2017 | Current use: Multifamily dwellings, existing | Permit id: Pmt2017-04210 |