Content | Date | Cost | Contractor Rank | Address | Contractor |
---|---|---|---|---|---|
SCORE 95 Rewiring for rooftop ac unit and installation of disconnect switch boxes at unit 115. Referencecpl2017-00802. A c unit must be identified with unit number. This is needed so that power can be safely shut off if any service work is needed. A c unit must have a means of disconnect within sight of equipment. This would be required on roof next to unit. All wiring must be run in approved conduit. Exposed romex shall not be used between the wall and the a c unit. Electrician needs to verify that breakers in panels are sized correctly. A service receptacle must be installed for service work. Client: Christophe Edwards | Permit type: Electrical | Permit status: Cmp | Completion date: October 2, 2017 | Current use: Multifamily dwellings, existing | Permit id: Pmt2017-03931 |